Product Number: 123105A

RS-485, 1 Pr, 22AWG, Str TC, PE Ins, OS+TC Brd, PVC Jkt, AIA, PVC Jkt, CM, PLTC, Sun Res

RS-485, 120 Ohm, 1 pair 22AWG (7x30) tinned copper Datalene® insulaton, Overall Foil + 65% Tinned Copper Braid, PVC jacket, Aluminum Interlocking Armor, PVC Jacket, CM, PLTC, SUN RES

  • Availability:
    Global
  • Global inventory:
    Available
123105A
  • Specifications
  • Resources

Specifications

Suitable Applications

exposure to rodent, crush, or cut through force, burial, serial communication (RS-485 standard) comprising of PLCs, VFDs, HMIs, motors, RTU, SCADA, etc. within noisy environments over long distance, outdoor such as solar, lighting, etc.

Conductor

Element No. of Elements Size Stranding Material
Pair(s) 1 22 AWG 7x30 TC - Tinned Copper

Insulation

Element Material Nom. Thickness Color Code Notes
Pair(s) PE - Polyethylene (Foam) 0.029 in (0.74 mm) White/Blue Stripe & Blue/White Stripe HDPE

Outer Shield

Shield Type Material Coverage Drainwire Type
Tape Bi-Laminate (Alum+Poly) 100% 22 AWG (7x30) TC
Braid Tinned Copper (TC) 65%

Inner Jacket

Material Nom. Diameter
PVC - Polyvinyl Chloride 0.281 in (7.14 mm)

Armor

Armor Type & Material
AIA - Aluminum Interlock Armor

Outer Jacket

Material Nom. Thickness Nom. Diameter
PVC - Polyvinyl Chloride 0.045 in (1.1 mm) 0.577 in (14.7 mm)

Overall Cable Diameter (Nominal)

0.577 in (14.7 mm)

Electricals

Element Nom. Conductor DCR Nom. Capacitance Cond-to-Cond Nom. Characteristic Impedence Nom. Velocity of Prop. Max. Current
Pair(s) 14.7 Ohm/1000ft (48.2 Ohm/km) 11 pF/ft (36 pF/m) 120 Ohm 78% 2.7 Amps per Conductor at 25ºC

Nom. Outer Shield DCR

2.8 Ohm/1000ft (9.2 Ohm/km)

High Frequency (Nominal/Typical)

Element Frequency [MHz] Nom. Insertion Loss (Attenuation)
Pair(s) 1 0.5 dB/100ft

Voltage

UL Voltage Rating
300 V (CM, PLTC)

Temperature

UL Temperature Operating
60°C -40°C to +60°C

Table Notes

-40C

Bend Radius

Stationary Min. Installation Min.
5.8 in (150 mm) 5.8 in

Max. Pull Tension

200 lbs (91 kg)

Bulk Cable Weight

140 lbs/1000ft (210 kg/km)

Environmental Suitability

Indoor, Sunlight Resistance

Flammability / Reaction to Fire

UL1685 UL Loading, 1202

NEC / UL Compliance

Article 725, Article 800

CEC / C(UL) Compliance

CMG HLBCD

European Directive Compliance

EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)

Update and Revision

Revision Number: 0.68 Revision Date: 05-05-2023

Update and Revision

Revision Number: 0.68 Revision Date: 05-05-2023