Product Number: 1360A
Fieldbus, 1 Pr #16 Str TC, PP Ins, OS, PVC Jkt, PLTC-ER, ITC-ER, c(UL)CMG
Fieldbus, 1 Pair 16AWG (7x24H) Tinned Copper, PP Insulation, Overall Beldfoil® Shield, Orange PVC Outer Jacket, PLTC-ER, ITC-ER, c(UL) CMG
-
Availability:
-
Global inventory:
Specifications
Product Overview
Suitable Applications |
harsh environment digital and serial two-way communication, oil and gas extraction and refining sites, petrochemical, Profibus process automation or Foundation FieldBus process automation, extreme temperature environments, exposure to humidity/moisture, dust, and oil, remote locations long distance applications, etc. |
---|
Construction Details
Conductor
Element | No. of Elements | Size | Stranding | Material |
---|---|---|---|---|
Pair(s) | 1 | 16 AWG | 7x24 | TC - Tinned Copper |
Insulation
Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
---|---|---|---|---|
Pair(s) | PP - Polypropylene | 0.029 in (0.74 mm) | 0.117 in (2.97 mm) | Blue & Orange |
Outer Shield
Shield Type | Material | Coverage | Drainwire Type | Notes |
---|---|---|---|---|
Tape | Bi-Laminate (Alum+Poly) | 100% | 20 AWG (7x28) TC | Foil In - with polyester wrap |
Outer Jacket
Material | Nom. Thickness | Nom. Diameter | Ripcord |
---|---|---|---|
PVC - Polyvinyl Chloride | 0.065 in (1.7 mm) | 0.40 in (10 mm) | Yes |
Overall Cable Diameter (Nominal) |
0.40 in (10 mm) |
---|
Electrical Characteristics
Electricals
Element | Nom. Conductor DCR | Max. Capacitance Unbalance | Nom. Capacitance Cond-to-Shield | Nom. Characteristic Impedence | Nom. Velocity of Prop. | Max. Current |
---|---|---|---|---|---|---|
Pair(s) | 5.9 Ohm/1000ft | 1.2 pF/ft (3.9 pF/m) | 45 pF/ft | 100 Ohm | 66% | 8 Amps per Conductor at 25ºC |
Nom. Outer Shield DCR |
7.5 Ohm/1000ft (25 Ohm/km) |
---|
High Frequency (Nominal/Typical)
Element | Frequency [MHz] | Nom. Insertion Loss (Attenuation) |
---|---|---|
Pair(s) | 0.039 | 0.08 dB/100ft |
High Frequency
Frequency [MHz] | Max. Insertion Loss (Attenuation) | Max./Min. Input Impedance (unFitted) [Ohm] |
---|---|---|
0.031 | 0.091 dB/100ft | 100 |
Voltage
UL Voltage Rating |
---|
300 V (CMG, PLTC-ER), 150 V (ITC-ER) |
Mechanical Characteristics
Temperature
UL Temperature | Operating |
---|---|
105°C | -40°C to +105°C |
Bend Radius
Stationary Min. | Installation Min. |
---|---|
4 in (100 mm) | 4 in (100 mm) |
Max. Pull Tension |
84 lbs (38 kg) |
---|---|
Bulk Cable Weight |
69 lbs/1000ft |
Standards and Compliance
Environmental Suitability |
Indoor, Outdoor, Sunlight Resistance, Oil Resistance, Burial |
---|---|
Flammability / Reaction to Fire |
UL 1685 UL Loading, FT4, IEEE 1202, IEC 60332-1-2 |
CPR Compliance |
CPR Euroclass: Eca |
NEC / UL Compliance |
Article 725, Article 727, Article 800, CM |
CEC / C(UL) Compliance |
CMG |
European Directive Compliance |
EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
UK Regulation Compliance |
UKCA Mark |
APAC Compliance |
China RoHS II (GB/T 26572-2011) |
Product Notes
Notes |
Fieldbus: Orange jacket. Profibus PA: Intrinsically Safe Blue jacket. |
---|
History
Update and Revision |
Revision Number: 0.512 Revision Date: 02-03-2025 |
---|
Information
Update and Revision |
Revision Number: 0.512 Revision Date: 02-03-2025 |
---|
Part Numbers
Item # | Color | Putup Type | Length | UPC | Footnote |
---|---|---|---|---|---|
1360A 0031000 | Orange | Reel | 1,000 ft | 612825112631 | C |