87761

Electronic, 2 C #22 Str TC, FEP Ins, OS, PVDF Jkt, CMP

...
High Temperature Electronic, 2 Conductor 22AWG (7x30) Tinned Copper, FEP Insulation, Overall Beldfoil® Shield, PVDF Outer Jacket, CMP
Request Sample Get Product Alerts

Specifications
Product Overview

Suitable Applications

extreme high temperature environments; chemical resistant; outdoor and burial applications; low voltage analog signals (4-20ma, 0-10v, ...); low voltage digital control (24v, …); line level audio; voice communications; panel wiring

Construction Details
Conductor
Element No. of Elements Size Stranding Material
Pair(s) 1 22 AWG 7x30 TC - Tinned Copper
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code
Pair(s) FEP - Fluorinated Ethylene Propylene 0.007 in (0.18 mm) 0.042 in (1.1 mm) Black, Red
Outer Shield
Shield Type Material Coverage Drainwire Type
Tape Bi-Laminate (Alum+Poly) 100% 22 AWG (7x30) TC
Outer Jacket
Material Nom. Thickness Nom. Diameter
PVDF - Polyvinylidene Fluoride 0.014 in (0.36 mm) 0.116 in (2.95 mm)

Overall Cable Diameter (Nominal)

0.116 in (2.95 mm)

Electrical Characteristics
Electricals
Element Nom. Conductor DCR Nom. Capacitance Cond-to-Cond Nom. Capacitance Cond-to-Other (Conds + Shield) Nom. Characteristic Impedence Max. Current
Pair(s) 18.2 Ohm/1000ft 35 pF/ft (110 pF/m) 67 pF/ft (220 pF/m) 42 Ohm 9 Amps per Conductor at 30ºC
Voltage
UL Voltage Rating
300 V (CMP)
Mechanical Characteristics
Temperature
UL Temperature Operating
150°C -20°C to +150°C
Bend Radius
Stationary Min. Installation Min.
1.2 in (30 mm) 1.2 in (30 mm)

Max. Pull Tension

27.3 lbs (12.4 kg)

Bulk Cable Weight

12 lbs/1000ft

Standards and Compliance

Environmental Suitability

Indoor, UV Resistance

Flammability / Reaction to Fire

NFPA 262, UL 910 (Plenum), FT6, IEC 60332-1-2

CPR Compliance

CPR Euroclass: Eca

NEC / UL Compliance

Article 800, CMP

CEC / C(UL) Compliance

CMP

European Directive Compliance

EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), REACH, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)

UK Regulation Compliance

UKCA Mark

APAC Compliance

China RoHS II (GB/T 26572-2011)

Non-Plenum Number

8761

History

Update and Revision

Revision Number: 0.529 Revision Date: 02-15-2024

Part Numbers
Item # Color Putup Type Length UPC Footnote
87761 002500 Red Reel 500 ft 612825216049 C
87761 0021000 Red Reel 1,000 ft 612825216032 C
87761 0025000 Red Reel 5,000 ft 612825216056