7704ELW

LonWorks, 2PR #22 Sol BC, PO ins, OS, LSNH Jkt, 300V, Cca

...
LonWorks, 2 Pair AWG 22 Bare Copper - Solid, Polyolefin (PO, PE, PP) insulation, Overall Beldfoil® shielding, LSZH / FRNC jacket , 300V, CPR Cca
Get Product Alerts

Specifications
Product Overview

Suitable Applications

LonWorks, instrumentation, Low capacitance

Physical Characteristics (Overall)
Conductor
AWG Stranding Material Nominal Diameter No. of Pairs
22 Solid BC - Bare Copper 0.64 mm 2

Conductor Count

4

Total Number of Pairs

2

Insulation
Material Nominal Diameter Min. Wall Thickness
PE - Polyethylene (Foam) 1.35 mm 0.3 mm
Color Chart
Number Color
Pair 1 White/Blue & Blue/White
Pair 2 Orange/White & White/Orange

Table Notes

Ring marking applied

Outer Shield
Type Material Coverage [%] Drainwire Material Drainwire Diameter Drainwire AWG
Tape Bi-Laminate (Alum+Poly) 100% TC - Tinned Copper 0.51 mm 24

Table Notes

Aluminum inside

Outer Jacket
Material Nominal Diameter Diameter +/- Tolerance Min. Wall Thickness
LSZH - Low Smoke Zero Halogen (Flame Retardant) 6.5 mm 0.4 mm 0.5 mm
Construction and Dimensions
Cabling
Description
2 pairs twisted to cable core
Electrical Characteristics
Conductor DCR
Nominal Conductor DCR Nominal Outer Shield DCR
55 Ohm/km 17 Ohm/km
Capacitance
Nom. Capacitance Conductor to Conductor Nom. Capacitance Conductor to Shield
40 pF/m 65 pF/m
Inductance
Nominal Pair Inductance
0.65 µH/m
Impedance
Frequency [MHz] Nominal Characteristic Impedance
1 - 20 100 Ohm
High Frequency (Nominal/Typical)
Frequency [MHz] Nom. Insertion Loss Nom. NEXT [dB]
0.772 MHz 1.8 dB/100m
1 MHz 2 dB/100m 59 dB
4 MHz 3.6 dB/100m 50 dB
10 MHz 5.5 dB/100m 44 dB
16 MHz 7 dB/100m 41 dB
20 MHz 7.8 dB/100m 40 dB
Current
Element Max. Recommended Current [A]
Conductor(s) 2.5 Amps per Conductor
Voltage
Voltage Rating [V]
300 V
Temperature Range

Operating Temperature Range

-15°C To +80°C

Mechanical Characteristics

Bulk Cable Weight

40.2 kg/km

Max. Pull Tension

50 N

Min. Bend Radius During Installation

80 mm

Standards

CPR Euroclass

Cca-s1,d1,a1

Applicable Environmental and Other Programs

Environmental Space

Indoor - Euroclass Cca

Flammability, LS0H, Toxicity Testing

IEC Flammability

IEC 60332-1-2

IEC 60754-1 - Halogen Amount

Zero

History

Update and Revision

Revision Number: 0.43 Revision Date: 06-28-2024

Part Numbers
Item #
7704ELW.00305