8471ELV

Electronic, 2 C #16 Str TC, LSZH Ins, LSZH Jkt, B2ca

...
Electronic, 2 Conductor 16AWG (19x29) Tinned Copper, LSZH Insulation, LSZH Outer Jacket, CPR B2ca
Request Sample Get Product Alerts

Specifications
Product Overview

Suitable Applications

low voltage analog signals (4-20ma, 0-10v, ...); low voltage digital control (24v, …); line level audio; computer communication; panel wiring

Physical Characteristics (Overall)
Conductor
AWG Stranding Material No. of Pairs
16 19x29 TC - Tinned Copper 1

Conductor Count

2

Total Number of Pairs

1

Insulation
Material Nominal Diameter Diameter +/- Tolerance Nominal Wall Thickness
PE - Polyethylene 2.67 mm 0.05 mm 0.018 in
Color Chart
Number Color
Pair 1 Black & White
Inner Shield
Material
No Shield
Inner Jacket
Nominal Wall Thickness
0.89 mm
Outer Shield
Material
No Shield
Outer Jacket
Material Nominal Diameter Nominal Wall Thickness
LSZH - Low Smoke Zero Halogen (Flame Retardant) 7.1 mm 0.89 mm
Construction and Dimensions
Stranding
Twists
6 twist/ft
Cabling
Description
1 pair covered with a polyester foil
Electrical Characteristics
Conductor DCR
Nominal Conductor DCR
14.7 Ohm/km
Capacitance
Nom. Capacitance Conductor to Conductor
52 pF/m
Inductance
Nominal Inductance Nominal Pair Inductance
0.17 µH/ft 0.62 µH/m
Current
Element Max. Recommended Current [A]
Conductor(s) 7.1 Amps per Conductor
Voltage
Voltage Rating [V]
300 V
Temperature Range

Installation Temperature Range

-15°C To +80°C

Storage Temperature Range

-45°C To +80°C

Operating Temp Range (Flexible Install)

-15°C To +80°C

Operating Temp Range (Fixed Install)

-45°C To +80°C

Mechanical Characteristics

Oil Resistance

IEC 60811-404

Max. Pull Tension

127 N

Min. Bend Radius During Installation

71 mm

Min. Bend Radius/Minor Axis

2.5 in

Standards

CPR Euroclass

B2ca-s1,d1,a1

CENELEC Compliance

EN 50290-2-20

Applicable Environmental and Other Programs

Environmental Space

Indoor - Euroclass B2ca

EU Directive Compliance

EU Directive 2003/11/EC (BFR)

EU CE Mark

Yes

Suitability

Suitability - Indoor

Yes

Suitability - Non-Halogenated

Yes

Suitability - Sunlight Resistance

Yes

Flammability, LS0H, Toxicity Testing

IEC Flammability

IEC 60332-1-2

IEC 60754-1 - Halogen Amount

Zero

IEC 60754-2 - Halogen Acid Gas Amount - Max. Conductivity

2.5 µS/mm

IEC 60754-2 - Halogen Acid Gas Amount - Min. pH

4.3

IEC 61034-2 - Smoke Density Min. Transmittance

60%

Plenum/Non-Plenum

Plenum (Y/N)

No

History

Update and Revision

Revision Number: 0.31 Revision Date: 03-21-2024

Part Numbers
Item #
8471ELV.00305
8471ELV.02305