9842LVS

RS-485, 2PR #24 Str TC, PO ins, F/B, LSNH Jkt, 300V, SWA, B2ca

9842LVS
RS-485, 2 Pair AWG 24 Tinned Copper - Stranded, Polyolefin (PO, PE, PP) insulation, Foil + Braid(s) shielding, LSZH / FRNC jacket , 300V, SWA, CPR B2ca
Get Product Alerts

Specifications
Product Overview

Suitable Applications

RS-485, POS; Computer communications; Low Voltage Analog Signals (4-20ma, 0-10v, ...); Low Voltage Digital Control (24v, …); Line Level Audio; Panel Wiring; serial communication (RS-485 standard) comprising of PLCs, VFDs, HMIs, motors, RTU, SCADA, etc. within noisy environments over long distance, etc.

Physical Characteristics (Overall)
Conductor
AWG Stranding Material No. of Pairs
24 7x32 TC - Tinned Copper 2

Conductor Count

4

Total Number of Pairs

2

Insulation
Material Nominal Diameter Diameter +/- Tolerance
PE - Polyethylene 1.73 mm 0.05 mm
Color Chart
Number Color
Pair 1 White/Blue & Blue/White
Pair 2 White/Orange & Orange/White
Inner Shield
Type Material Material Trade Name Coverage [%] Drainwire Material Drainwire AWG
Tape Bi-Laminate (Alum+Poly) Beldfoil® (Z-Fold®) TC - Tinned Copper AWG24/7
Braid Tinned Copper (TC) 100%
Inner Jacket
Material Color Nominal Diameter Nominal Wall Thickness
LSZH - Low Smoke Zero Halogen (Flame Retardant) Chrome (RAL 7037) 8.65 mm 1.1 mm

Table Notes

UV Stabilised

Outer Shield
Type Material Material Trade Name Drainwire Material
Tape Beldfoil® (Z-Fold®) TC - Tinned Copper
Braid Tinned Copper (TC)
Outer Jacket
Material Nominal Diameter Nominal Wall Thickness
LSZH - Low Smoke Zero Halogen (Flame Retardant) 13.1 mm 1.35 mm
Construction and Dimensions
Cabling
Description
2 pairs and 2 fillers twisted to cable core
Armor
Type of Armor Material Thickness of Armoring Wires Coverage Percentage
Steel Wire Armoring Galvanized steel wire 0.9 mm Min. 95%
Electrical Characteristics
Conductor DCR
Nominal Conductor DCR Nominal Outer Shield DCR
78.7 Ohm/km 7.2 Ohm/km
Capacitance
Nom. Capacitance Conductor to Conductor Nom. Capacitance Conductor to Other Conductor to Shield
42 pF/m 75.5 pF/m
Impedance
Frequency [MHz] Nominal Characteristic Impedance
1 MHz 120 Ohm
High Frequency (Nominal/Typical)
Frequency [MHz] Nom. Insertion Loss
1 MHz 1.97 dB/100m
Delay
Nominal Delay Nominal Velocity of Propagation (VP) [%]
520 ns/ft 66%
Current
Element Max. Recommended Current [A]
Conductor(s) 2.1 Amps per Conductor
Voltage
Voltage Rating [V]
300 V
Temperature Range

Installation Temperature Range

-15°C To +80°C

Storage Temperature Range

-45°C To +80°C

Operating Temp Range (Flexible Install)

-15°C To +80°C

Operating Temp Range (Fixed Install)

-45°C To +80°C

Mechanical Characteristics

Oil Resistance

IEC 60811-404

Min. Bend Radius During Installation

196.5 mm

Standards

CPR Euroclass

B2ca-s1a,d1,a1

CENELEC Compliance

EN 50290-2-20

Other Specification

DMX-512

Applicable Environmental and Other Programs

Environmental Space

Indoor, Indoor/Outdoor, Outdoor, Indoor/Outdoor - Euroclass B2ca

EU CE Mark

Yes

Suitability

Suitability - Indoor

Yes

Suitability - Non-Halogenated

Yes

Suitability - Oil Resistance

Yes

Suitability - Outdoor

Yes

Suitability - Sunlight Resistance

Yes

Flammability, LS0H, Toxicity Testing

IEC Flammability

IEC 60332-1-2, IEC 60332-3-24

IEC 60754-1 - Halogen Amount

Zero

IEC 60754-2 - Halogen Acid Gas Amount - Max. Conductivity

2.5 µS/mm

IEC 60754-2 - Halogen Acid Gas Amount - Min. pH

4.3

IEC 61034-2 - Smoke Density Min. Transmittance

60%

History

Update and Revision

Revision Number: 0.60 Revision Date: 06-28-2024

Part Numbers
Item # Color Put-Up Type Length EAN
9842LVS.00500
9842LVS.001000 Black Reel 1,000 m 8719605176219