3107ELS

RS-485, 2PR #22 Str TC, PO ins, F/B, LSNH Jkt, SWA

3107ELS
RS-485, 2 Pair AWG 22 Tinned Copper - Stranded, Polyolefin (PO, PE, PP) insulation, Foil + Braid(s) shielding, LSZH / FRNC jacket ,SWA

Regions Available: Global
Get Product Alerts

Specifications
Product Overview

Suitable Applications

Instrumentation and computer cable. For EIA RS-485 transmissions applications

Construction Details
Conductor
Element No. of Elements Size Stranding Material
Pair(s) 2 22 AWG 7x30 TC - Tinned Copper
Insulation
Element Material Nom. Thickness Nom. Insulation Diameter Color Code
Pair(s) PE - Polyethylene (Foam) 0.65 mm (0.026 in) 2.04 mm (0.0803 in) White/Blue & Blue/White, White/Orange & Orange/White
Outer Shield
Shield Type Material Coverage Drainwire Type
Tape Bi-Laminate (Alum+Poly) 100% 22 AWG (7x30) TC
Braid Tinned Copper (TC) 65%
Inner Jacket
Material Nom. Thickness Nom. Diameter
LSZH - Low Smoke Zero Halogen (Flame Retardant) 1.35 mm (0.0531 in) 8.9 mm (0.35 in)
Armor
Armor Type & Material Armor Thickness Coverage
SWA - Steel Wire Armor 0.9 mm (0.035 in) Min. 95%
Outer Jacket
Material Nom. Thickness Nom. Diameter
LSZH - Low Smoke Zero Halogen (Flame Retardant) 1.35 mm (0.0531 in) 13.3 mm (0.524 in)

Overall Cable Diameter (Nominal)

13.3 mm (0.524 in)

Electrical Characteristics
Electricals
Element Nom. Conductor DCR Nom. Capacitance Cond-to-Cond Nom. Capacitance Cond-to-Other (Conds + Shield) Nom. Characteristic Impedence Nom. Velocity of Prop. Max. Current
Pair(s) 48.2 Ohm/km (14.7 Ohm/1000ft) 36.1 pF/m (11.0 pF/ft) 68.6 pF/m 120 Ohm 78% 2.1 Amps per Conductor

Nom. Outer Shield DCR

5.9 Ohm/km (1.8 Ohm/1000ft)

High Frequency (Nominal/Typical)
Element Frequency [MHz] Nom. Insertion Loss (Attenuation)
Pair(s) 1 1.64 dB/100m (0.500 dB/100ft)
Voltage
Voltage Rating
300 V
Mechanical Characteristics
Temperature
Operating Installation Storage
-45°C To +80°C -15°C To +80°C -45°C To +80°C
Bend Radius
Stationary Min. Installation Min.
200 mm (7.9 in) 260 mm (10 in)

Max. Pull Tension

290 N (65 lbf)

Bulk Cable Weight

316 kg/km (212 lbs/1000ft)

Standards and Compliance

Environmental Suitability

IndoorIndoor/OutdoorOutdoorIndoor/Outdoor - Euroclass Eca, Indoor, Outdoor, Non-Halogenated, Sunlight Resistance, Oil Resistance

Flammability / Reaction to Fire

IEC 60332-1-2

ISO/IEC Compliance

IEC 61034-2 - Smoke Density Min Transmittance = 60%

CENELEC Compliance

EN 50290-2-20

European Halogen Free Standards

IEC 62821-1 Halogen Free Compliance = Yes, IEC 60754-1 - Halogen Amount = Zero, IEC 60754-2 - Halogen Acid Gas Amount - Max. Conductivity = 2.5 µS/mm, IEC 60754-2 - Halogen Acid Gas Amount - Min. pH = 4.3

UK Regulation Compliance

UKCA Mark

Other Standard Compliance(s)

DMX-512

History

Update and Revision

Revision Number: 0.132 Revision Date: 04-08-2025

Part Numbers
Item # Color Putup Type Length EAN
3107ELS.00500 Black Reel 500 m
3107ELS.001000 Black Reel 1,000 m 8719605160508
3107ELS.001500 Black Reel 1,500 m 8719605195623